The messages in the following sections are logged to the BASEstar Classic history file by the DAS for AB INTERCHANGE software. These messages are logged to provide more detailed diagnostic information than what is supplied by the returned status values.
Messages logged to the history file for DAS for AB INTERCHANGE software use event class 21 and event type 2.
To view all messages logged by this DAS use the following syntax:
$ BSTAR BSTAR> SHOW HISTORY/EVENT=21.2.* |
The following messages are logged by the Network Interface (NI).
Connection made with server DCM_DTL$SRV_!UL.
Explanation: Success. A connection has been made by
the DAS to the indicated DTL server process. At this point, a
connection to the actual PLC has not yet been established.
User Action: None.
Disconnect from server DCM_DTL$SRV_!UL.
Explanation: Error. The indicated server process has
disconnected from the DAS. The disconnect usually is caused by an
abnormal termination of the server process, but could also be because
of a BASEstar shutdown or because someone intentionally shut down the
server process.
User Action: Examine the log file of the server
process and the history file to determine the cause of the server
shutdown and then take corrective action based on the error found.
License not found for DAS for INTERCHANGE software.
Explanation: Error. A valid license hasn't been loaded
for the DAS.
User Action: Obtain a valid license and load it onto
the system where the DAS is running.
Starting DTL server process DCM_DTL$SRV_!UL.
Explanation: Informational. The DAS is attempting to
start the DTL server process.
User Action: None.
DCM_DTL$SRV_!UL did not start in time, aborting associated connections.
Explanation: Error. The indicated server process did
not start within the allotted time (59 seconds), or if the server
started, it did not successfully establish a connection with the DAS.
User Action: Examine the DTL server log file and the
history file to determine if any errors were logged by the server
process. Take action based on the errors found.
D.2 PE Logged Messages
The following messages are logged by the Protocol Emulator (PE).
Device address string too long: !/ "!AD"
Explanation: Error. A point address is too long to fit
into the space allocated for it in the DAS. The DAS allows 18
characters for the point address.
User Action: Use a shorter address for the point.
Invalid qualifier: !AD
Explanation: Error. An invalid qualifier has been
specified in an upload or download request. The qualifier in error is
logged.
User Action: Consult the DAS guide to determine valid
qualifiers for the command being requested.
Device MODEL definition is !AD family; Actual PLC TYPES is !AD.
Explanation: Error. When reading the status from a
PLC, the DAS determined that the model for the actual PLC does not
match the model of the PLC definition.
User Action: Modify the device definition to match the
actual model of the PLC.
Error in the device network address !AD and or model !AD.
Explanation: Error. The DAS detected an error in the
model or network address for the device.
User Action: If the model is invalid, use one of the
predefined DTL types when creating the device. If the network address
is invalid, see the DAS guide for information on the proper syntax for
a network address for this DAS.
Model !AD not supported.
Explanation: Error. The model in the device definition
is not supported by the DAS.
User Action: Use one of the predefined DTL types from
the DCM_DTL_CONFIG.TEMPLATE file when creating the device.
Error converting read data for address !AD.
Explanation: Error. An error occurred when doing data
conversion for the address indicated. The conversion error is probably
due to incompatible data types between the request and the data in the
PLC.
User Action: Use a different data type when requesting
the data.
Error converting write data for address !AD.
Explanation: Error. An error occurred when doing data
conversion for the address indicated. The conversion error is probably
due to incompatible data types between the request and the data in the
PLC.
User Action: Use a different data type when writing
the data.
D.3 DTL Server Logged Messages
The following messages are logged by the DTL server process. All messages first log the server that generated the error before the actual error message is logged. INTERCHANGE software can return four types of error codes as follows:
DTL DAS server process shut down abnormally.
Explanation: Error. The server process is shutting
down due to an unrecoverable error. The history file should also have
logged the error that caused the shutdown.
User Action: Examine the history file for the error
that caused the termination and take action based on the error found.
DTL DAS disconnected circuit from server process.
Explanation: Error. The DAS has disconnected from the
server process. The cause is probably because of an abnormal shutdown
of the ILAN$DEVSRV process.
User Action: Examine the history file for any errors
logged that might account for the abnormal shutdown. Also examine the
ILAN$DEVSRV log, error and ACCVIO files for causes for the shutdown.
Restart ILAN$DEVSRV.
Error calling DTL_DIAG_STATUS.
Explanation: Error. An error occurred when requesting
status information from the PLC.
User Action: Examine the error message returned and
take action based on the error found.
DTL_C_DEFINE error.!/!AD
Explanation: Error. An error occurred when defining a
point for reading or writing. A point must be defined before it can be
read or written. The message logs the address part of the string passed
to the DTL_C_DEFINE routine.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
Error calling DTL_DOWNLOAD.
Explanation: Error. An error occurred when downloading
a file to the PLC.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
Error calling DTL_CONNECT for EI !AD.
Explanation: Error. An error occurred when attempting
to connect to the indicated Ethernet Interface. A connection must be
established with the Ethernet Interface before any subsequent requests
can be processed.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
Error calling DTL_DISCONNECT.
Explanation: Error. An error occurred when attempting
to disconnect from the indicated Ethernet Interface.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
Disconnected from EI !AD.
Explanation: Informational. The DTL server process
successfully disconnected from the indicated Ethernet Interface.
User Action: None.
DTL_READ error. Address: !AD.
Explanation: Error. An error occurred when attempting
to read data from a PLC. The data table address from which the read was
attempted is also logged.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
DTL_UNDEF error. Address: !AD.
Explanation: Error. An error occurred when attempting
to undefine an address. The address that was being undefined is logged
in the message. Solicited points are undefined when the number of
solicited points (controlled by ILAN$DTL_MAX_ELEMENTS) is exceeded.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
DTL_WRITE error. Address: !AD.
Explanation: Error. An error occurred when attempting
to write data to a PLC. The data table address to which the write was
attempted is also logged.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
Established connection to EI !AD.
Explanation: Informational. The DTL server process
successfully connected to the indicated Ethernet Interface. A
connection must be established to the Ethernet Interface before any
subsequent operations can take place.
User Action: None.
Lost connection to EI !AD.
Explanation: Error. The connection to the indicated
Ethernet Interface has been broken. The most likely causes are that the
PLC has been powered down or there has been a break in the network
connection to the PLC.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
Unsolicited exception. Unsol ID: !OW.
Explanation: Error. An error occurred when receiving
unsolicited data. The most likely cause of this error is that two hosts
have defined points with the same unsolicited ID on the same PLC.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
DTL DAS server process running.
Explanation: Informational. The server process was
started successfully and is now running.
User Action: None.
Max queued for this run: !UL.
Explanation: Informational. This message is logged
when the server process is shut down. It logs the maximum number of
requests that were queued (i.e. requested but not yet processed) since
the DTL server process was first started. If this number is large, then
more requests are being received than can be processed by the PLC.
User Action: None.
DTL server process shut down.
Explanation: Informational. The DTL server process has
successfully finished shutting down.
User Action: None.
NOS error X!XL.
Explanation: Error. A Data Highway Plus error occurred
that was not translated by the INTERCHANGE software into a DTL error code.
User Action: See Appendix B of the INTERCHANGE Software Reference Manual for a
description of the error code and take action based on the error.
Unsolicited write. No unsolicited definition found for ID: !OW.
Explanation: Error. Unsolicited data was received, but
the DTL server process has no record of requesting unsolicited data for
the indicated unsolicited ID. This error is most likely to occur when a
device is disabled and the unsolicited point has been cancelled, but
the Ethernet Interface is still sending unsolicited data to the host.
User Action: If the problem persists, the PLC may need
to be reset to cancel the sending of the unsolicited data. If the
problem does not persist, then no action needs to be taken.
DTL server process shutting down.
Explanation: Informational. The DTL server process has
received a request to shut down and is starting the shutdown process.
User Action: None.
DTL_UNSOL_DEF error defining ID: !OW on EI: !AD.
Explanation: Error. An error occurred when attempting
to define an unsolicited point. Unsolicited points must be defined
before unsolicited data will be sent by the Ethernet Interface.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
DTL_UNDEF error. Unsol ID: !OW.
Explanation: Error. An error occurred when attempting
to undefine an unsolicited point. Unsolicited points are undefined when
a device is disabled or a point is deleted.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.
Error calling DTL_UPLOAD.
Explanation: Error. An error occurred when uploading a
file from the PLC.
User Action: Examine the error returned by
INTERCHANGE software and take action based on the error.