Previous | Contents | Index |
Table 1-1 lists MMS client supported services. See the Industrial automation systems - Manufacturing Message Specification Part 1: Service definition for a definition of the MMS services.
MMS Service | BASEstar Classic DCM Function |
---|---|
Identify | Read Status |
Status | Read Status |
GetCapabilityList | Read Status |
ReadVariable | Read Data |
WriteVariable | Write Data |
InformationReport | Unsolicited Data Management |
GetNameList | Directory |
InitiateDownloadSequence | Download |
DownloadSegment | Download |
TerminateDownloadSequence | Download |
InitiateUploadSequence | Upload |
UploadSegment | Upload |
TerminateUploadSequence | Upload |
CreateProgramInvocation | Start Program |
DeleteProgramInvocation | Stop Program |
Start | Start Program |
Stop | Stop Program |
Reset | Stop Program |
UnsolicitedStatus | Log Service |
Initiate | Enable Device |
Conclude | Disable Device |
Abort | Disable Device |
Table 1-2 lists the MMS conformance building blocks. See the Industrial automation systems - Manufacturing Message Specification Part 1: Service definition for information on conformance building blocks.
Proposed CBBs | |
---|---|
STR1 | Y |
STR2 | Y |
NEST | 10 |
VNAM | Y |
VADR | Y |
Max Segment Size | 512 1 |
Version | 0/1 |
The DAS for OMNI software supports the following BASEstar Classic functions using SINEC-AP and SINEC-H1 compliant devices:
TABLE Table 1-3 lists SINEC-AP and SINEC-H1 client supported services. See the Industrial automation systems - Manufacturing Message Specification Part 1: Service definition for a definition of the MMS services.
SINEC-AP and SINEC-H1 Service | BASEstar Classic DCM Service |
---|---|
Identify | Read Status |
Status | Read Status |
GetCapabilityList | Read Status |
ReadVariable | Read Data |
WriteVariable | Write Data |
InformationReport | Unsolicited Device Connect Management |
GetNameList | Directory |
InitiateDownloadSequence | Download |
DownloadSegment | Download |
TerminateDownloadSequence | Download |
InitiateUploadSequence | Upload |
UploadSegment | Upload |
TerminateUploadSequence | Upload |
CreateProgramInvocation | Start Program |
DeleteProgramInvocation | Stop Program |
Start | Start Program |
Stop | Stop Program |
Reset | Stop Program |
UnsolicitedStatus | Log Service |
Initiate | Enable Device |
Conclude | Disable Device |
Abort | Disable Device |
Table 1-4 lists the SINEC-AP and SINEC-H1 conformance building blocks. See the Industrial automation systems - Manufacturing Message Specification Part 1: Service definition for information on conformance building blocks.
Proposed CBBs | |
---|---|
STR1 | Y |
STR2 | Y |
NEST | 10 |
VNAM | Y |
VADR | Y |
Max Segment Size | 4096 1 |
The DAS for OMNI software supports the following BASEstar Classic functions using SINEC-S7 compliant devices:
TABLE Table 1-5 lists SINEC-S7 client supported services. See the Industrial automation systems - Manufacturing Message Specification Part 1: Service definition for a definition of the MMS services.
SINEC-S7 Service | BASEstar Classic DCM Service |
---|---|
Identify | Read Status |
Status | Read Status |
ReadVariable | Read Data |
WriteVariable | Write Data |
InformationReport | Unsolicited Device Connect Management |
UnsolicitedStatus | Log Service |
Initiate | Enable Device |
Abort | Disable Device |
Table 1-6 lists the SINEC-S7 conformance building blocks. See the Industrial automation systems - Manufacturing Message Specification Part 1: Service definition for information on conformance building blocks.
Proposed CBBs | |
---|---|
STR1 | Y |
STR2 | Y |
NEST | 10 |
VNAM | N |
VADR | Y |
Max Segment Size | 4096 1 |
The MMS specification provides a rich variety of device/application functions of which only a sub-set are typically supported by MMS/AP/S7/H1 devices, typically MAP Classes 2 or 3.
The DAS for OMNI software can act as a MMS Server for a subset of MMS functions, ie. read, write and status.
For detailed information about the supported functions, see Chapter 3.